Rated Tripping Current | 10/20/30/200/300/500mA |
---|---|
Fault Condition Settings | × 1/2, × 1, × 5, × DC, AUTO RAMP |
Trip Current Duration | 1000ms, 200ms (×5) |
Lowest Resolution | 1ms |
Trip Time Accuracy | ±0.6%rdg±4dgt |
Operating Voltage | 230V+10%-15% (195V – 253V) 50Hz |
Safety Standard | IEC 61557-1,-6 IEC 61010-1 CAT III 300V IEC 61010-2-031 Pollution Degree 2 |
Withstand Voltage | 3700V AC for 1 minute |
IP Rating | IEC 60529-IP54 |
Dimensions | 167(L) × 186(W) × 89(D)mm |
Weight | 800g approx. |
Accessories | Molded plug test leads* 9121 (Shoulder Strap) 9147 (Cord case) Instruction Manual |
Optional | 7121B (Simplified measurement probe) |
Kyoritsu 5406A RCD Testers
All orders are processed upon receipt. Please allow 2 – 3 business days for processing.
Processing and shipping time estimates do not account for holidays and weekend.
0 in stock
Backorder available. Kindly email us to check on the lead time
• Custom microprocessor controlled for highest accuracy and reliability.
• 3 LEDs for checking correct wiring status.
• 0 and 180 degree phase angle switch permits quick tests and consistent readings.
• Digital read-out of tripping time.
• Constant current source circuitry ensures that a fluctuating mains voltage does not affect the accuracy of readings.
• Large custom digital display readout.
• Visual indication of reversed phase and neutral wiring at socket.
• Designed to IP54 Rating.
• Complies with IEC 61557
• Test of a large kind of RCD’s: Standard, Selective, AC and A (DC sensitive breakers)